 RSI-95
Description
The Gamewell-FCI 600 Series analog addressable Fire Alarm Control Panel (FACP) will provide all of the required functions to control the releasing of bulk fire suppressant materials. The Gamewell-FCI 600 Series analog addressable FACPs are currently listed for NFPA 13 Sprinkler, NFPA 15 Water Spray, NFPA 11 Low-Expansion Foam, NFPA 16 Water Foam, NFPA 17 Dry Chemical, and NFPA 2001 Clean Agent types of suppressant. The GamewellFCI Releasing Solenoid Interface (RSI-95) is an intelligent addressable interface for the remote control and supervision of activation solenoids used in releasing applications. The Releasing Solenoid Interface (RSI-95) is an addressable Releasing Service Module, providing intelligent analog addressable control functionality complete with full solenoid supervision and transient voltage suppression. Only the RSI-95 can be used to actuate the releasing solenoid. The RSI-95 is automatically bypassed during a SmartStartTM or circuit initialization to prevent accidental discharge during the generic configuration, should inputs be inadvertently activated. The analog addressable RSI-95 solenoid control module is designed for use with any 600 Series FACP. To avoid unplanned fire suppressant release, the RSI-95 assembly is the ONLY assembly to be used to provide remote releasing solenoid control. The circuit can control up to two amps of DC power to the solenoid. The RSI-95 is powered and controlled via the analog addressable signaling line circuit and the solenoid power is obtained from the control panel or a UL-Listed fire protection 24 VDC power supply. The RSI-95 fully supervises the releasing solenoid.
Releasing Solenoid Interface
RSI-95
Features
* * * * * * * Compatible with the Gamewell-FCI 600 Series analog addressable fire alarm control panels. Provides full solenoid supervision. Transient voltage suppression. Mounts in its own unique base. Automatic bypass at system start-up. 2.0 A of DC power for solenoid. Types of Suppressants: - NFPA 13 Sprinkler. - NFPA 15 Water Spray. - NFPA 11 Low Expansion. - NFPA 16 Water Foam. - NFPA 17 Dry Chemical. - NFPA 2001 Clean Agent. NOTE: Releasing systems must be designed by properly qualified personnel.
Installation Guideline
Install the RSI-95 according to NFPA 70, NEC 760, and any applicable local codes. NOTE: Only one each RSI-95 and solenoid may be connected together for each releasing circuit. The RSI-95 is designed to fit on a 4.688" (11.908 cm) by 2.125" (5.397 cm) deep electrical box (user supplied).
SmartStartTM is a trademark of Honeywell International Inc.
An ISO 9000-2000 Company
SIGNALING
S521
GAMEWELL-FCI
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. (c)2007 Honeywell International Inc. All rights reserved. www.gamewell-fci.com CS-2046 Rev. A page 1 of 2
12 Clintonville Road, Northford, CT 06472-1610 USA * Tel: (203) 484-7161 * Fax: (203) 484-7118
CS-2064ph1.wmf
Installation Guideline (Continued)
The addition of the trim ring (P/N 70839) allows flush installation. The total voltage drop from the power supply to the end of the solenoid circuit shall not exceed two volts. The RSI-95 must have its address programmed before the system will operate correctly.
Ordering Information
Model
RSI-95
Description
RSI-95 assembly consists of an RSM-95 analog addressable Releasing Service Module and integral SID Solenoid Interface Device. NOTE: RSM-95 and SID no longer available separately. Flush trim ring for RSM-95.
Installation
Connect the system wiring to the four-position terminal block L1, L2, P1, P2 per wiring diagram A-W532-1. Connect the solenoid device wiring to the four-position terminal block per wiring diagram A-W572. IMPORTANT! Maximum L1 - L2 loop resistance should not be more than 25 ohms. 70839
CAUTION: No wiring connections should be made while the system is powered.
Specifications
Temperature: Humidity: Power: +P and -P, or +24 and -24: Normal Current: Alarm Current: Solenoid Circuit Rating: Mounting: 0C to 49C (32F to 120F) 85%, non-condensing 21 VDC from analog addressable module. 24 VDC from UL-Listed power source. 6.5 mA 6.5 mA + solenoid load 2.0 A power-limited steady operation 4.0" (10.16 cm), 4.688" (11.908 cm), double-gang electrical box
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA * Tel: (203) 484-7161 * Fax: (203) 484-7118 www.gamewell-fci.com CS-2046 Rev. A page 2 of 2